top of page
APC Symmetra LX 4kVA Scalable to 8kVA N+1, 220/2

APC Symmetra LX 4kVA Scalable to 8kVA N+1, 220/2

$14,800.00Price
•Scalability
•Scalable power capacity
•Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
•Scalable runtime
•Allows additional run time to be quickly added as needed.
•Plug-and-Play external batteries
•Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
•Field-replaceable power distribution panel
•Ensures compatibility with equipment that has different plug types.
•Programmable frequency
•Ensures compatibility with different input frequencies.
•Availability
•Hot-swappable batteries
•Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
•Power Modules connected in parallel
•Enhances availability by allowing immediate, seamless recovery from isolated module failures.
•Battery modules connected in parallel
•Delivers higher availability through redundant batteries.
•Automatic internal bypass
•Supplies utility power to the connected loads in the event of a UPS power overload or fault.
•Modular design
•Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
•Automatic restart of loads after UPS shutdown
•Automatically starts up the connected equipment upon the return of utility power.
•Hot-swappable intelligence modules
•Ensures clean, uninterrupted power to protected equipment during Intelligence Module replacement.
•Hot-swappable power modules
•Ensures clean, uninterrupted power to protected equipment during Power Module replacement.
•Configurable for N+1 internal redundancy
•Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
•Redundant Intelligence Modules
•Provides higher availability to the UPS connected loads by giving redundant communication paths to critical UPS functions
  • Details

    •Output power capacity
    •2.8 KWatts / 4.0 kVA
    •Max Configurable Power (Watts)
    •5.6 KWatts / 8.0 kVA
    •Nominal Output Voltage
    •230V
    •Output Voltage Note
    •Configurable for 220 : 230 or 240 nominal output voltage
    •Output Voltage Distortion
    •Less than 5% at full load
    •Output Frequency (sync to mains)
    •47 - 63 Hz
    •Output Frequency (not synced)
    •60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
    •Other Output Voltages
    •220, 240
    •Load Crest Factor
    •up to 5 : 1
    •Topology
    •Double Conversion Online
    •Waveform type
    •Sine wave
    •Maximum Output Current
    •18
    •Output Connections
    •Hard Wire 3-wire (H N + G) (Battery Backup)
    •Bypass
    •Internal Bypass (Automatic and Manual)
    •Input
    •Nominal Input Voltage
    •230V , 400V 3PH
    •Input frequency
    •45 - 65 Hz (auto sensing)
    •Input Connections
    •Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
    •Input voltage range for main operations
    •155 - 276 (1:1), 290 - 480 (3:1)V
    •Input Total Harmonic Distortion
    •Less than 7% for full load
    •Other Input Voltages
    •220V, 240V, 380V, 415V
    •Input Power Factor at Full Load
    •0.98
    •Batteries & Runtime
    •Battery type
    •Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
    •Included Battery Modules
    •1
    •Typical recharge time
    •3hour(s)
    •Battery Slots Empty
    •1
    •Expected Battery Life (years)
    •3 - 5
    •Extendable Run Time
    •1
    •Battery Volt-Amp-Hour Capacity
    •864
    •Extended Run Options
    •APC-Symmetra-LX-4kVA-Scalable-to-8kVA-N-1-220-230-240V-or-380-400-415V
    • Communications & Management
    •Interface Port(s)
    •DB-9 RS-232 , Smart-Slot
    •Pre-Installed SmartSlot™ Cards
    •AP9631
    •Control panel
    •Multi-function LCD status and control console
    •Audible Alarm
    •Audible and visible alarms prioritized by severity
    •Emergency Power Off (EPO)
    •Yes
    •Available SmartSlot™ Interface Quantity
bottom of page